Vertiv Liebert HIPULSE-U UPS 30kVA–500kVA Online Double-Conversion UPS

The Vertiv Liebert HIPULSE-U UPS is a fully digital, three-phase power protection platform designed for demanding data centres, industrial facilities and mission-critical applications. Twin DSP control, 0.9 output power factor and scalable configurations support reliable power protection from 30kVA to 500kVA.

Twin DSP digital control 0.9 output power factor 30kVA to 500kVA range
VERTIV
LIEBERT HIPULSE-U
SCALABLE
500kVA Maximum capacity
30–500kVA Wide capacity range
0.9 PF Output power factor
Twin DSP Fully digital control
VFI Online double conversion
Product Overview

Liebert HIPULSE-U UPS for Mission-Critical Power

The Vertiv Liebert HIPULSE-U UPS is a three-phase online uninterruptible power supply available in capacities from 30kVA to 500kVA. It is designed to protect data centres, industrial systems and other critical applications against interruptions and power-quality disturbances.

Its online double-conversion architecture uses an IGBT-based PWM inverter to continuously condition incoming power before supplying connected equipment. A fully digital twin-DSP control platform manages the UPS operating functions and power-conversion stages.

A rated output power factor of 0.9 enables the UPS to deliver increased active power for modern equipment loads. The system can also handle leading power-factor loads without kW derating under the conditions specified by Vertiv.

The broad 323–478V AC input window and 45–65Hz input frequency range help the UPS remain on utility power during voltage and frequency variations, reducing unnecessary battery discharge.

The Liebert HIPULSE-U is engineered for demanding load conditions, including high crest-factor loads, fully non-linear loads and fully unbalanced loads. It also provides substantial inverter and static-bypass overload capability.

Built-in maintenance bypass, front-access servicing, parallel configurations and dual-bus architecture help support availability, maintainability and future capacity expansion.

Key Advantages

Reliable, Scalable and Digitally Controlled UPS Protection

The Liebert HIPULSE-U combines digital control, robust overload performance, flexible system architecture and maintainable cabinet design.

Twin DSP Digital Control

Dual digital signal processors provide fully digital supervision of power conversion, protection and UPS operating functions.

Online Double Conversion

The IGBT-based PWM inverter continuously conditions utility power before supplying connected critical equipment.

0.9 Output Power Factor

The 0.9 output power factor enables the UPS to deliver greater active-power capacity for modern equipment loads.

Wide Input Tolerance

A 323–478V AC input range and 45–65Hz frequency tolerance support operation during utility-power variations.

Flexible System Architecture

Parallel, hot-standby and dual-bus configurations support capacity growth and redundancy requirements.

Front-Access Maintenance

Front access for component replacement and preventive maintenance helps simplify servicing and reduce required service clearance.

AC INPUT 323–478V
RECTIFIER AC to DC
IGBT PWM DC to AC
LOAD Protected AC
DSP 1
Power Control
DSP 2
System Control
Fully Digital Twin-DSP Architecture Continuous double-conversion power processing with digitally controlled rectifier, inverter, bypass and system-protection functions.
Power Conversion and Control

Twin DSP Control with IGBT-Based PWM Inverter

The Liebert HIPULSE-U combines fully digital control with online double-conversion technology to provide regulated output power for sensitive and mission-critical equipment.

  • Fully digital twin-DSP control
  • Online double-conversion operation
  • IGBT-based PWM inverter
  • 0.9 rated output power factor
  • 323–478V AC input voltage range
  • 45–65Hz input frequency range
  • Built-in maintenance bypass
  • Adjustable bypass synchronisation window
  • Short-circuit-proof inverter
  • Integrated back-feed contacts
Recommended Applications

High-Capacity UPS Protection for Critical Infrastructure

Enterprise Data Centres Three-phase online protection for servers, storage platforms and network infrastructure.
Banking and Finance Reliable power continuity for transaction, settlement and financial-processing systems.
Telecommunication Networks Protected power for communication, switching and network-management infrastructure.
Healthcare Facilities Power protection for critical healthcare IT and supporting technology systems.
Manufacturing Plants UPS protection for process-control, automation and industrial computing systems.
Government Facilities Reliable continuity for public-sector data, communication and security systems.
Retail Infrastructure Centralised UPS protection for business systems, logistics and transaction platforms.
Education and Research Power continuity for institutional data centres, laboratories and digital infrastructure.
Technology and Configuration

Liebert HIPULSE-U UPS Technology

A scalable power-protection platform with robust load handling, flexible communication and multiple high-availability configurations.

30–500kVA Twin DSP Online Double Conversion IGBT PWM Inverter 0.9 Output PF 323–478V Input 45–65Hz Input Three Phase 100% Non-Linear Load 100% Unbalanced Load Built-In Maintenance Bypass Dual Bus Architecture Up to 6 Parallel Units Modbus Jbus SNMP
Technical Information

Liebert HIPULSE-U UPS Specifications

Review the capacity, electrical, load-handling, communication and system-architecture specifications of the Vertiv Liebert HIPULSE-U UPS.

Manufacturer
Vertiv
Brand
Liebert
Product family
HIPULSE-U
Product type
Three-phase online uninterruptible power supply
Available nominal ratings
30, 40, 60, 80, 120, 160, 200, 300, 400 and 500kVA
UPS topology
Online double conversion
Control architecture
Fully digital twin-DSP control
Inverter technology
IGBT-based PWM inverter
Rectifier type
6-pulse for 30–400kVA; 12-pulse for 500kVA
Nominal input voltage
380/400/415V AC
Input voltage range
323–478V AC
Nominal input frequency
50/60Hz
Input frequency range
45–65Hz
Nominal output voltage
380/400/415V AC, three phase
Output power factor
0.9
Steady-state voltage stability
±1%
Transient voltage stability
±5%
Transient recovery time
Up to 20 milliseconds
Internal frequency stability
±0.1%
Bypass synchronisation window
Adjustable up to ±6%
UPS overload: 101–110%
60 minutes
UPS overload: 111–125%
10 minutes
UPS overload: 126–150%
1 minute
Static bypass short-duration capacity
Up to 14 times rated current for 10 milliseconds
Static bypass overload capacity
Up to 10 times rated current for 100 milliseconds
Linear-load voltage distortion
Less than 1%
Non-linear-load voltage distortion
Less than 5%
Non-linear load capability
100%
Permissible load unbalance
100%
High crest-factor loads
Supported
Leading power-factor loads
Supported without kW derating under specified conditions
Phase-angle accuracy
±1° with balanced or fully unbalanced loads
Maintenance bypass
Built in
Maintenance access
Front access
Parallel configuration
Up to six UPS units
Supported architectures
Parallel, 1+N, hot standby and dual bus
Load bus synchronisation
Supported through LBS architecture
Field communication protocols
Modbus and Jbus
Network monitoring protocol
SNMP
Battery testing
Automatic battery testing
Battery protection
Deep-discharge protection
Battery charging
Selectable boost-charging duration
Optional battery feature
Temperature-compensated battery charging
Inverter protection
Short-circuit proof
Back-feed protection interface
Integrated potential-free contacts
General UPS safety standard
IEC 62040-1
EMC standard
IEC 62040-2
UPS classification
IEC 62040-3, VFI-SS-111
Frequently Asked Questions

Liebert HIPULSE-U UPS FAQs

Important information about capacity, topology, load-handling performance and communication support.

What capacities are available in the Liebert HIPULSE-U UPS range?

The Liebert HIPULSE-U family is available in 30, 40, 60, 80, 120, 160, 200, 300, 400 and 500kVA nominal ratings.

What topology does the Liebert HIPULSE-U use?

It uses online double-conversion topology with a fully digital twin-DSP control system and an IGBT-based PWM inverter.

Can the HIPULSE-U handle non-linear and unbalanced loads?

Yes. The UPS is designed to support high crest-factor loads, fully non-linear loads and fully unbalanced loads.

Which communication protocols are supported?

The Liebert HIPULSE-U supports Modbus and Jbus field communication and SNMP-based network monitoring and management.

Product Architecture

Liebert HIPULSE-U UPS System Views

Explore the cabinet design, dual-bus architecture and digital monitoring configuration of the HIPULSE-U platform.

Request Liebert HIPULSE-U UPS Pricing

Contact Intermax for Liebert HIPULSE-U UPS pricing, availability and product information.

Contact Intermax

Get Quote